Select . The transmitter will automatically inhibit the 4-24mA output to avoid false alarms.

The sensor enters a warm-up phase (countdown timer varies by sensor type). The output signal is locked at 4mA (or a designated fault current) during this period.

Touch the wand to the four magnetic switches on the glass display: Up , Down , Escape (X) , and Enter (✓) .

Review the full technical manual for site-specific safety regulations. Xnx Universal Transmitter Quick Start Guide

Detailed navigation instructions are provided in the full technical manual.

Press to save, turn off the gas, and remove the adapter. Fault Codes and Troubleshooting

Ensure the sensor environment is completely free of the target gas. If pure background air cannot be guaranteed, apply zero-grade air from a calibration cylinder at a flow rate of 500 mL/min. Select

Wiring diagrams for analog loops Share public link

Remove the protective cap from the sensor body, align the keyed pins of the plug-in cartridge, and push it firmly into place.

Disconnect all power sources before opening the transmitter enclosure. The output signal is locked at 4mA (or

: The XNX cover must be fully seated with a minimum of 9 threads engaged to maintain its explosion-proof rating.

Disconnect the gas supply. The XNX will temporarily hold the 4-20mA output in a "Maintenance" state to prevent false alarms at your controller while the residual gas clears from the sensor. 7. Basic Troubleshooting and Fault Codes